Mechanical values and environment | |
---|---|
Design | E |
Material | |
Cable material | PVC |
Housing material | Fiber glass reinforced PPS |
Weight | |
Net | 0,29 kg |
Ambient temperature | -20 ... 60 °C |
Degree of protection | IP67 |
Resilience to vibration | In acc. with EN 60947-5-2 |
Mechanical life | 100 x 106 |
Installation position | Any, pay attention to marking During mounting it is to be ensured the marking arrows on actuator and read head are opposite each other. |
Tightening torque | 0,4 ... 0,5 Nm |
Number of NC contacts | 1 NC contact |
Number of NO contacts | 1 NO contact |
Connection | Hard-wired encapsulated cable with cable end sleeves 0.34mm2 |
Cable length | 5 m |
Method of operation | Magnetic, reed contact |
Electrical connection ratings | |
Rated insulation voltage Ui | 26,4 V DC |
Rated impulse withstand voltage Uimp | 1,5 kV |
Switching voltage | 24 V |
Switching current | 8 ... 500 mA |
Switching characteristics | NO + NC |
Switching voltage according to UL | |
According to UL Class 2 | AC/DCmax.24 V |
Operating distance | |
Repeat accuracy R | max.10 % |
Assured switch-off distance Sar | 17 mm The assured switch-off distance s_ar corresponds to the reset distance. |
Assured operating distance Sao | 6 mm Figure only applies if there is no ferromagnetic material in the vicinity of the read head and the actuator. |
Miscellaneous | |
in compliance with | EN ISO 13849-1:2015{} EN 50178:1997{} EN 60204-1:2006/A1:2009{} EN ISO 14119:2013{} EN 61000-6-2:2005{} EN 61000-6-3:2007/A1:2011{} EN 60947-5-3:2013 |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |